MCB (Miniature circuit breaker) is a re-settable device designed to protect a circuit from short circuits and overcurrents. Trip curves of MCB’s (B, C, D, K and Z curves) tell us about the trip current rating of Miniature Circuit breakers. Trip current rating is the minimum current at which the MCB will trip instantaneously. It is required that the trip current must persist for 0.1s.

Technical parameters:

Net length 86mm
Net width 36mm
Net height 77mm
Net weight 0.19kg
Power loss 3.80W - 10W
Min. ambient temperature -35°C
Max. ambient temperature 70°C
Tripping characteristics C
Amperage 6A-63A
Poles 1+N
Product category AM10
Series AMPARO
Rated breaking capacity 10kA
Version AC-MCB
Product standard EN 60898
Packaging units 1 pc, 6 pc, 90 pc

The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection.TRIP CURVE CLASS B

 

TRIP CURVE CLASS C

MCB with class C trip characteristics trips instantaneously when the current flowing through it reaches between 5 to 10 times the rated current. Suitable Domestic and residential applications and electromagnetic starting loads with medium starting currents.

 

TRIP CURVE CLASS D

MCB with class D trip characteristics trips instantaneously when the current flowing through it reaches between Above 10(excluding 10) to 20 times the rated current. Suitable for inductive and motor loads with high starting currents.

 

TRIP CURVE CLASS K

MCB with class K trip characteristics trips instantaneously when the current flowing through it reaches between 8 to 12 times the rated current. Suitable for inductive and motor loads with high inrush currents.

 

TRIP CURVE CLASS Z

MCB with class Z trip characteristics trips instantaneously when the current flowing through it reaches between 2 to 3 times the rated current. These type of MCBs are highly sensitive to short circuit and are used for the protection of highly sensitive devices such as semiconductor devices.

 

TRIP CURVE CLASS A

MCB with class A trip characteristics trips instantaneously when the current flowing through it reaches between 2 to 3 times the rated current. As like Class Z MCBs, these are also highly sensitive to short circuit and are used for the protection of semiconductor devices.

 

 

Manufacturer Code:
AM017606
Standard :
EN 60898 Electrical accessories. Circuit-breakers for overcurrent protection for household and similar installations.